Troubleshooting Common Electrical Control System Faults of Catalytic Combustion Equipment

2026-10-28 09:09:55 Puhua Tech 8
Home News Troubleshooting Common Electrical Control System Faults of Catalytic Combustion Equipment
Puhua Tech Launches New High-Efficiency RTO System for Chemical Industry

Many manufacturing plants rely on catalytic combustion equipment to handle organic waste gas and meet emission standards. The electrical control system is the core brain of RCO catalytic combustion devices, responsible for temperature monitoring, fan adjustment, interlock protection and automatic operation. Once the control system fails, the whole VOCs treatment line will stop running, which may bring production interruption and compliance risks. This practical guide sorts out typical faults, inspection steps and handling suggestions for the electric control system of catalytic combustion equipment, helping on-site engineers locate problems quickly and safely.

Overview of the Catalytic Combustion Electrical Control System

A standard control system for catalytic combustion equipment consists of PLC controller, HMI touch screen, thermocouple temperature sensors, pressure transmitters, frequency converters, solenoid valves, flame detectors and safety interlock circuits. All signals are collected and processed by the PLC, and the system will trigger alarm or shutdown actions when temperature, air volume or flame state exceeds the preset safe range.

Zhengzhou Puhua Technology is a professional environmental protection equipment manufacturer in Henan. The company focuses on the design, research, development and production of dust control equipment, desulfurization equipment, denitrification equipment, VOCs organic waste gas treatment equipment, pneumatic conveying equipment and wastewater treatment equipment. Its product portfolio includes baghouse dust collectors, RCO catalytic combustion equipment, RTO equipment, VOCs governance systems, desulfurization towers, denitrification devices, photocatalytic oxidation equipment, pulse dust collectors, mobile dust collectors, ultra-low emission facilities and wastewater treatment equipment. The electric control configuration of its self-developed RCO catalytic combustion equipment adopts mature PLC control schemes, with complete safety interlock logic and convenient on-site maintenance interface.

Safety Precautions Before Troubleshooting

Electrical inspection of catalytic combustion equipment involves high-voltage circuits and combustible gas pipelines. Operators must follow these rules before checking any fault:

  1. Cut off the main power supply of the control cabinet and hang a warning sign for maintenance operation.

  2. Confirm that the waste gas intake valve is closed and complete the purging process to eliminate residual organic gas inside the furnace.

  3. Wear insulated tools and protective equipment, do not touch exposed terminals with wet hands.

  4. Record the current alarm code and operating parameters on HMI before resetting any fault.

  5. Do not short-circuit safety interlock switches for temporary operation.

Common Fault Classification and Troubleshooting Steps

1. Power Supply and PLC Startup Faults

Symptoms: The control cabinet has no display, the PLC cannot power on, or the power indicator flashes abnormally.

  • Check the input voltage of the main power and 24V DC power module, confirm whether the circuit breaker or fuse is tripped or blown.

  • Check whether the wiring terminals of the power supply are loose, burnt or oxidized due to long-term heating.

  • Check the heat dissipation condition inside the control cabinet. Dust accumulation and high ambient temperature will lead to unstable power module output.

  • Verify whether the PLC status light shows a running state; if the fault light keeps on, download the program log for further analysis.

2. Temperature Signal Abnormality

Symptoms: Temperature reading jumps sharply, displays over-limit value, or keeps unchanged while the actual furnace temperature changes.

Fault phenomenonPossible causesTreatment method
Temperature value fluctuates violentlyThermocouple shielding wire grounding failure, signal line interferenceRearrange signal cables separately from power cables, recheck shielding grounding terminal
No temperature feedbackThermocouple wire broken, loose terminal, sensor burnoutReplace damaged thermocouple and rewire according to the marking sequence
Continuous high temperature alarmSensor attached with carbon deposit, signal drift, catalyst channel blockageClean the probe surface, calibrate the sensor, check the internal blockage of the catalytic chamber

3. Fan and Frequency Converter Control Faults

Symptoms: The fan cannot start, the fan speed cannot be adjusted, or the system reports air pressure interlock alarm.

  • Check the frequency converter fault code, common alarms include overcurrent, overload and overheating.

  • Confirm whether the start signal from PLC to the frequency converter is normally transmitted, test the dry contact output signal.

  • Check the air pressure switch and air duct pressure sampling pipe. Blocked sampling pipes will cause false air shortage alarms.

  • Check the mechanical rotation of the fan impeller and bearing, and eliminate mechanical jamming before electrical debugging.

4. Ignition and Flame Detection Faults

Symptoms: Ignition failure, flame alarm appears immediately after ignition, automatic lockout after repeated ignition attempts.

  • Check the ignition transformer and ignition electrode, clean the carbon deposit on the electrode and adjust the spark gap.

  • Inspect the flame detector lens, dust and oil pollution will weaken the flame signal and trigger false flame loss alarm.

  • Check the solenoid valve of the fuel pipeline, confirm whether the valve can open and close smoothly after receiving the control signal.

  • Check the gas pressure to ensure the fuel supply pressure stays within the normal working range.

5. HMI Communication and Signal Interlock Faults

Symptoms: The touch screen fails to communicate with PLC, data cannot refresh, safety interlock alarm cannot be cleared.

  • Check the communication cable between HMI and PLC, confirm the connector is fastened and free from corrosion.

  • Compare the communication parameters including station number, baud rate and protocol settings.

  • Check all safety interlock points one by one, including fire door limit, air pressure interlock, temperature high limit and emergency stop button.

  • Eliminate the fault point corresponding to the interlock alarm first, then perform manual reset operation.

Regular Maintenance Checklist for Electric Control System

Regular maintenance can reduce unexpected downtime of catalytic combustion equipment. Operators can follow this checklist for periodic inspection:

  1. Clean dust inside the control cabinet every month, check the cooling fan and filter cotton of the cabinet.

  2. Tighten all wiring terminals quarterly, check for heating and discoloration of terminals.

  3. Calibrate temperature sensors and pressure transmitters regularly.

  4. Test emergency stop buttons and safety interlock functions monthly.

  5. Backup PLC program and HMI parameter files after each parameter modification.

When users purchase RCO catalytic combustion equipment from Zhengzhou Puhua Technology, the technical team will provide operation training for the on-site control system, including daily parameter checking, common alarm identification and standard maintenance suggestions. For complex electrical control failures that cannot be solved on site, you can contact the technical service team for remote guidance or on-site inspection support.

Most electrical control faults of catalytic combustion equipment come from loose wiring, sensor pollution, power instability and interlock signal abnormality. Following the sequence of checking power supply first, then signal collection and finally actuators can greatly improve troubleshooting efficiency. Stable operation of the electric control system is the foundation for long-term and reliable VOCs waste gas treatment. Selecting well-configured catalytic combustion equipment and carrying out standardized daily maintenance will help enterprises maintain stable emission performance and reduce maintenance costs.

Share this article

Related Articles

Subscribe to Our Newsletter

Stay updated with the latest news and insights from Puhua Tech.

Online customer service system

Troubleshooting Common Electrical Control System Faults of Catalytic Combustion Equipment Frequently Asked Questions

What does Zhengzhou Puhua Technology Co., Ltd. manufacture?

Zhengzhou Puhua Technology Co., Ltd., founded in 2008 and based in the Zhengzhou High-Tech Development Zone, manufactures industrial environmental protection equipment, including VOCs waste gas treatment systems, industrial dust collectors and solid waste processing equipment.

Do you support customised, non-standard equipment?

Yes. When standard models cannot meet site conditions, equipment is engineered to the actual air volume, pollutant concentration, gas temperature and available footprint, including explosion-proof, anti-corrosion and high-temperature options.

What information is required for a quotation?

Air volume (m3/h), pollutant composition and inlet concentration (mg/m3), gas temperature and humidity, dust load and particle size distribution, daily operating hours, site dimensions, and the applicable emission standard.

What does the cooperation process look like?

Condition survey, proposal and quotation, contract, manufacturing, delivery, installation guidance and commissioning, operator training and acceptance, then after-sales service.